Discrete I/O number | 16 | |
Number of I/O expansion modules | <= 4 suitable for transistor output <= 4 suitable for relay output | |
Power supply voltage range | 85...264 V | |
Network frequency | 50/60 Hz | |
Instantaneous peak current | <= 40 A | |
Power consumption VA | <= 49 VA on 100...240 V maximum number of I/O expansion modules <= 33 VA on 100...240 V without I/O expansion modules | |
Power output current | 0.325 A on 5 V for expansion bus 0.12 A on 24 V for expansion bus | |
Discrete input logic | Sink or source (positive/negative) | |
Discrete input voltage | 24 V | |
Discrete input voltage type | Direct current | |
Analog input resolution | 10 bits | |
LSB value | 10 mV | |
Conversion time | 1 ms per channel + 1 controller cycle time for analog input | |
Permissible overload at the input | +/- 30 V DC for analog input and 5 minutes maximum +/- 13 V DC for analog input constant | |
Voltage state 1 guarantee | >= 15 V applicable input | |
Voltage state 0 guarantee | <= 5 V applicable input | |
Discrete input current | 7 mA for discrete input 5 mA for fast input | |
input resistance | 4.9 kOhm for fast input 3.4 kOhm for discrete input 100 kOhm for analog input | |
Response time | 10 ms open operation suitable for output 35 µs close operation suitable input; I2...I5 terminal 10 ms close operation suitable for output 5 µs open operation suitable for fast input; I0, I1, I6, I7 terminal 35 µs open operation suitable input; other terminals terminal 5 µs off operation for fast input; I0, I1, I6, I7 terminal 100 µs off operation for input; other terminals terminal | |
Configurable filter time | 0 ms for input 12 ms for input 3 ms for input | |
Output voltage limit | 125 V DC 277 V AC | |
Connection type-terminal connection | 6 A on COM 1 termnal 7 A on COM 0 termnal | |
Absolute accuracy error | +/- 1% of full scale for analog input | |
Electrical life | Inductive load AC-15, (cos phi = 0.35) 240 V / 120 VA: 100000 times resistive (load) DC-12, 24 V / 48 W: 100000 times resistive (load) AC-12, 120 V / 240 VA: 100000 cycles of inductive load AC-15, (cos phi = 0.35) 240 V / 36 VA: 300,000 cycles of resistive (load) AC-12, 120 V / 80 VA: 300,000 cycles of inductive load (L/R = 7 ms ) DC-13, 24 V / 24 W: 100000 cycles resistive (load) DC-12, 24 V / 16 W: 300,000 cycles inductive (L/R = 7 ms) DC-13, 24 V / 7.2 W: 300,000 times inductive load AC-14, (cos phi = 0.7) 240 V / 240 VA: 100000 times inductive load AC-15, (cos phi = 0.35) 120 V / 60 VA: 100000 times inductive load AC-14, (cos phi = 0.7) 240 V / 72 VA: 300,000 times inductive load AC-15, (cos phi = 0.35) 120 V / 18 VA: 300,000 times resistive (load) AC-12, 240 V / 480 VA: 100000 times inductive Load AC-14, (cos phi = 0.7) 120 V / 120 VA: 100000 times Resistive (load) AC-12, 240 V / 160 VA: 300,000 times inductive load AC-14, (cos phi = 0.7) 120 V / 36 VA: 300,000 times | |
operating frequency | 20 switching operations/minute with maximum load | |
Mechanical life | >= 20000000 times applicable relay output | |
Minimum load | 1 mA at 5 V DC for relay output | |
Type of protection | Unprotected on 5 A | |
Reset time | 1 s | |
storage | 256 kB for user application and data RAM and 10000 instructions 256 kB for internal variables RAM | |
data backup | 256 kB built-in flash memory for backup of application and data | |
Data storage device | 2 GB SD card optional | |
Battery Type | BR2033 lithium non-rechargeable, battery life: 4 years | |
Cumulative running time | 1 year at 25 °C by interrupting the power supply | |
1K instruction execution time | 0.3 ms for events and periodic tasks | |
_ | 0.2 µs Boolean | |
Execution time of each task | 60 µs response time | |
Maximum target area size | 512 %M memory bits 8000 %MW memory words 255 %C counters 255 %TM timers 512 %KW constant words | |
Real Time Clock | Have | |
Clock error | <= 30 s/month at 25 °C | |
Control loop | Adjustable PID regulator up to 14 synchronous cycles | |
Calculate the number of inputs | 4 Fast input (high counting mode) (counting frequency: 100 kHz), counting capacity: 32 bits | |
Control signal type | Single phase A/B pulse/direction | |
Integrated connection type | USB port with connector mini B USB 2.0 Ethernet with connector RJ45 non-isolated serial link "serial 1" with connector RJ45 and interface RS232/RS485 | |
power supply | Serial The serial link is powered at 5 V 200 mA | |
Transfer rate | 1.2...115.2 kbit/s (default 115.2 kbit/s) for bus length... 15 m-communication protocol: RS485 1.2...115.2 kbit/s (default 115.2 kbit/s) for bus length... 3 m-Communication protocol: RS232 480 Mbit/s-Communication protocol: USB | |
Protocol | USB port: USB protocol-SoMachine-Network non-isolated serial link: Modbus protocol master/slave-RTU/ASCII or SoMachine-Network : Ethernet protocol | |
Ethernet port | 10BASE-T/100BASE-TX 1 port and 100 m copper cable | |
Communication service | Modbus TCP slave device DHCP client Ehternet/IP converter Modbus TCP server Modbus TCP client | |
Local signal | 1 LED green for accessible SD card (SD) 1 LED red for BAT per channel 1 LED green for I/O status 1 LED green for SL Ethernet network activity green for ACT Ethernet network connection yellow applicable link (link status) 1 LED red applicable module error (ERR) 1 LED green applicable PWR 1 LED green applicable RUN | |
Electrical connections | Mini B USB 2.0 connector to a programming terminal terminal block, 3 terminals for connecting 24 V DC power connector, 4 terminals for analogue inputs Removable screw terminal for input and removable screw terminal for output | |
cable length | <= 10 m shielded cable for fast input <= 30 m unshielded cable for output <= 30 m unshielded cable for digital signal input <= 1 m unshielded cable for analog input | |
isolation | 2300 V AC between output and internal logic Non-insulated between analogue inputs 500 V AC between input and internal logic Non-insulated between analogue inputs and internal logic 1500 V AC between supply and ground 500 V AC between sensor power supply and ground 500 V AC between input and ground 1500 V AC between output and ground 2300 V AC between supply and internal logic 500 V AC between sensor power supply and internal logic 500 V AC between Ethernet terminal and internal logic 2300 V AC between supply and sensor power supply | |
Logo | CE | |
Sensor power supply | 24 V DC at 250 mA supplied by the controller | |
Installation method | Top hat type TH35-15 Rail installation conforms to IEC 60715 Top hat type TH35-7.5 Rail installation conforms to IEC 60715 board or board with fixing kit | |
high | 90 mm | |
depth | 70 mm | |
width | 95 mm | |
product weight | 0.346 kg | |