EAU01 Intelligent AC Power Distribution Monitoring Module
The main functions are as follows:
1 . Analog quantity detection: detection of 6- phase AC voltage, 3- phase AC current, active power, reactive power, apparent power, power factor, frequency, and period.
2 . Switch quantity detection: detect 6- channel switch quantity signals.
3 . Automatic control: According to the AC input voltage information, the two-way AC input is controlled through the switching of the contactor. The contactor adopts the high-pressure pull-in-low-pressure hold mode.
There are two control logic modes: ATS and automatic switching.
4 . Communication function: Provide RS485 and CAN two communication ports.
5 . Alarm function: report abnormal phenomena to the main monitoring module, and indicate through alarm lights on this machine.
6 . Meter display: You can take the initiative to send the measurement data to the meter.
The external dimensions of EAU01 are: 117mm (width) × 88mm (height) × 119.5mm (depth).
Power supply input range:
80Vdc ~320Vdc or 80Vac ~295Vac (Rated voltage range: 180Vdc ~250Vdc/180Vac ~250Vac )