Power LEDs
K-bus
Bus Coupler
supply
Input for
power contacts
Power contacts
Fieldbus connection
Address selector
Configuration interface
BK5110, BK5120 | CANopen Bus Couplers
The BK51x0 Bus Couplers connect the CAN bus system to the electronic terminal blocks, which can be extended in modular fashion. One unit consists of one Bus Coupler, any number of up to 64 terminals and one end terminal. The BK5110 “Economy” variant permits particularly economical creation of peripheral interfacing connections. Up to 64 digital input/output terminals can be connected.
With the K-bus extension technology, the “Economy plus” Bus Coupler BK5120 allows the connection of up to 255 spatially distributed Bus Terminals to one Bus Coupler. The Bus Coupler works on the CAN protocol basis as defined in ISO 11898. In addition to network services, CANopen also determines the data allocation for automation systems applications and has established itself as an open CAN application layer. The Bus Couplers support all types of CANopen communications and can also be used without difficulty in manufacturer-specific CAN environments due to the simple structure of this protocol definition. The firmware can be updated via the configuration interface.
Parameterising can also be carried out using any CANopen configuration tools. For this, EDS data files are available, which describe all the setting options for the CANopen coupler. For most applications, however, no configuration is necessary, as CANopen provides practical default values for all parameters.