  •  Temperature Controller
    First, use
           BWY (WTYK)—803, 802 series pressure type temperature indicating controller (hereinafter referred to as temperature controller) is mainly designed for measuring and controlling the oil temperature of large power transformers, and also used for temperature detection and control of other equipment.
    This series of thermostats has good protection performance and can work normally under outdoor conditions for a long time. The instrument is equipped with two or three sets of large-capacity temperature-control switches, which can be used for the startup, shutdown and signal alarm of the transformer cooling system. At the same time, the temperature signal can be transmitted to the control center and the transformer oil temperature can be displayed synchronously.
    Serial number
    Model and name
    The main purpose
    Applications
    1
    BWY (WTYK) - 803, 
    802 thermostat
    Measure the top oil temperature of the transformer and start, shut down the cooling system and send an alarm signal when the temperature reaches the set value
    1000kVA or more transformer
    2
    BWY (WTYK) - 803, 
    802 (TH) thermostat
    Same as 1
    And suitable for wet tropical occasions
    1000kVA
    Above transformer
    3
    BWY (WTYK) - 803, 
    802 (TH) thermostat
    Same as 2; and using composite temperature sensor technology, 
     can simultaneously output Pt100 thermal resistance signal
    8000kVA
    Above transformer
    4
    XMT
    Digital display temperature controller
    It is matched with BWY (WTYK)-803 and 802A to 
    realize remote control of oil temperature telemetry. 
     Can also output standard signals for networking with computers
    8000kVA
    Above transformer
    5
    BWY (WTYK) - 803, 802A / XMT thermostat
     
     
    Can be replaced at the same time as 3, 4, etc.
    1) WTZK-02 thermostat
     2) Resistance thermometer
     3) Transfer switch
     4) XCT or XMT, etc.
    5) Transmitter
    8000kVA or above transformer or unattended substation
     
     
     

    Tình trạng sản phẩm:


    Second, the main technical parameters
    (1) BWY (WTYK) - 803, 802 type
             1, normal working conditions: ambient temperature -20 ° C ~ +55 ° C
                                           Relative humidity 5%~95%
             2. Measurement range: (0-100) °C (0-120) °C (0-150) °C
             3, indicating accuracy: 1.5
             4, temperature measuring parts: temperature package dimensions (Φ14 × 150) mm, the material is stainless steel, mounting thread M27 × 2
             5. Switching performance: Setting range: full scale Setting accuracy: ±3°C Switching difference: (6±2) °C
                      Rated power: AC 250V 3A DC 250V 50W
                      Standard set point: 803 K1=55°C K2=65°C K3=80°C   
                                    802 K1=55°C K2=80°C
             6, instrument installation size: compatible with WTYK-02.
     
             7. Outdoor performance: The waterproof and waterproof performance of the thermostat meets the requirements of IP55 in GB4208-93.
     
    (B) BWY (WTYK) - 803, 802 (TH) type
          1~6 with the same
          Outdoor performance: in line with GB/T2433.3-93 "Electrical and electronic products basic environmental test specifications test Ca:
                    Constant Damp Heat Test Method" Mildew resistance of exposed parts.
    (3) BWY (WTYK) - 803, 802A (TH)
          Same as above, with Pt 100 platinum resistance output. 
     
    XMT series thermometer
           1. Display method: three and a half digits
           2. Display error: ± (0.5% F.S + 1 word) ± (1% F.S + 1 word) second file
           3. Set point deviation: less than ± 1% FS
           4. Control point insensitive area: less than ±0.5% FS
           5. Output signal error: less than ±1% FS
           6. Output contact capacity: AC220V 3A (resistive load)
           7. Temperature coefficient: deviate from 20 °C ± 2 °C in the range of 0 °C - 50 °C
                      Its temperature coefficient is less than 0.05% / °C
           8. Industrial power supply: 220V ± 10% 50Hz, power consumption is less than 5W
           9. Working environment: non-corrosive gas with temperature 0°C-50°C and relative humidity≤85%
           10. Dimensions: 160 × 80 × 150 opening size: 152 +1 × 76 +1
           11. Weight: about 3kg
         

     



    TÂN THÀNH CAM KẾT

    • Sản phẩm, hàng hóa chính hãng.
    • Giá cả cạnh tranh.
    • Dịch vụ chăm sóc khách hàng tận tâm.

    Thông Tin Công Ty

    Đã thông báo

     


    THÔNG TIN LIÊN HỆ:
    -------------------------------
    CÔNG TY TNHH THIẾT BỊ CÔNG NGHIỆP TTH
    Trụ sở: số 124 ngõ 79 Yên Hoà-Cầu giấy-HN
    Kinh doanh 1 : 0816.861.515
    Kinh doanh 2 : 0836.861.515
    Email: tthkinhdoanh@gmail.com
    Email: tthkinhdoanh01@gmail.com

  • Kết nối với chúng tôi