Intermediate relay_Static intermediate relay ZJS-411,412,413,414,415,611,612
1. Rated value: rated voltage DC/AC48V, 110V, 220V, rated current: 0.25A, 1A, 2A, 4A.
2. Action value: The operating voltage should work reliably within the range of 30%-70% of rated voltage, and the operating current should be no more than 80% of rated current.
3. Return value: The return voltage should be no less than 10% of the rated voltage. ZJB and ZJS should be no less than 3% of the rated voltage (the power-off delay is not required).
4. Hold value: keep current and keep voltage at 75% of rated value.
5. Contact capacity: When the circuit is below 250V (internal constant is 5±0.75mS), the main contact is 50W/250VA, and the long-term allowable current of the contact is 5A.
6, power consumption: the rated voltage is not more than 5W.
7. Delay range: 0.02-5.00 seconds.
8. Insulation voltage: All circuits of the relay are resistant to AC 50HZ between the outer casing and the non-charged metal parts, and the circuits that are not electrically connected. The voltage of 2KV is tested for 1 minute without breakdown.