Product Description |
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
General specifications |
Signal type | Digital Input |
Supply |
Connection | Terminals 23, 24 |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
Rated current | Approx. 100 mA |
Power loss/power consumption | ≤ 1.8 W ; 2 VA / 1.8 W ; 2 VA |
Input |
Connection | Input I: 2-wire sensor: terminals 1+, 3-three wire sensor: terminals 1+, 2- and 3 input II: terminals 13+, 14- start-up override; |
Line fault detection | Breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA |
Input I | 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
| Open circuit voltage/short-circuit current | 22 V / 40 mA |
| Input resistance | 4.7 kΩ |
| Switching point/switching hysteresis | Logic 1: > 2.5 mA ; logic 0: < 1.9 mA |
| Pulse duration | > 50 μs |
| Input frequency | 0.001 ... 12000 Hz |
| Lead monitoring | Breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
Input II | Startup override: 1 ... 1000 s, adjustable in steps of 1 s |
| Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA |
| Open circuit voltage/short-circuit current | 18 V / 5 mA |
Output |
Connection | Output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 |
Output I, II | Signal, relay |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A |
| Mechanical life | 5 x 10 7 switching cycles |
| Energized/De-energized delay | Approx. 20 ms / approx. 20 ms |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Low voltage | |
| Directive 2006/95/EC | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Protection degree | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree | IP20 |
Mass | 300 g |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3 |
Mounting | On 35 mm DIN mounting rail acc. to EN 60715:2001 |