Rated operating voltage [Ue] | Power circuit: <= 300 V power circuit: <= 1000 V | |
Motor power (kW) | 30 kW (220/240 V) AC-3 55 kW (380/400 V) AC-3 59 kW (415/440 V) AC-3 75 kW (500 V) AC-3 80 kW (660/690 V) AC-3 18.5 kW (400 V) AC-4 75 kW (1000 V) AC-3 | |
Electrical life | 1.4 kA2.s (AC-3) 0.5 kA2.s (AC-1) 0.9 kA2.s (AC-3) | |
Mechanical life | 8 kA2.s | |
Maximum operating frequency | 2400 times per hour (ambient temperature <= 60 °C) | |
Action time | Breaking: 6...20 ms Closed: 20...50 ms | |
Control voltage limit | Release: 0.3...0.5 Uc 50/60 Hz Operation: 0.8...1.15 Uc 50/60 Hz | |
(~50Hz hold) power consumption (VA) | 2...18 VA 50 Hz 2...18 VA 60 Hz | |
Appointment of heating current [Ith] | Power circuit: 200 A (θ<= 60 °C) | |
Average impedance | 0.6 mΩ (Ith 50 Hz) | |
Heat dissipation | 3...8 W (50/60 Hz) | |
Rated short-time withstand current [Icw] | Power circuit: 1100 A, Duration: 1 s (<= 40 °C) Power circuit: 950 A, Duration: 10 s (<= 40 °C) Power circuit: 550 A, Duration: 1 minute (<= 40 °C) Power Circuit: 250 A, Duration: 10 minutes (<= 40 °C) | |
Fuses for use with relays | Power supply circuit: gG 250 A, type 1, U<= 690 V power supply circuit: gG 200 A, type 2, U<= 690 V | |
Overvoltage category | III | |
Rated insulation voltage [Ui] | Power circuit: 1000 V, in accordance with IEC 60947-4-1 | |
Surge suppression module | No built-in surge suppression module | |
Installation method | Rail mounting base plate installation | |
Wiring capability | Control circuit: screw-fastened, 2 cable 1...2.5 mm2, flexible cable, with twisted wire terminal. Control circuit: screw-fastened, 1 cable 1...2.5 mm2, soft wire, without twisting wire terminal. Control Circuit: screw-fastened, 2 cable 1...2.5 mm2, flexible cable, without twisted wire terminal. Control circuit: screw-fastened, 1 cable 1...2.5 mm2, flexible cable, with twisted wire terminal. Control circuit : Bolt-fastened, 1 cable 1...2.5 mm2, hard-wired, without twisted wire terminals. Control circuit: screw-fastened, 2 cable 1...2.5 mm2, hard-wired, without twist-wire terminal. Power circuit : Busbar terminals, hardwired, 5 x 25 mm power supply circuit: Terminals, 1 cable 10...120 mm2 lug outer diameter Ø: 25 mm, flexible cord, without twisting wire terminals. Power supply circuit: Terminals, 2 Cable 10...50 mm2 lug outside diameter Ø: 25 mm, cord, without twisting wire terminal. Power supply circuit: Terminals, 1 Cable 10...120 mm2 Wiring outside diameter Ø: 25 mm, cord , with twisted wire terminals. Power supply circuit: Terminals, 2 cable 10...50 mm2 lug outer diameter Ø: 25 mm, cord, with twisted wire terminals. Power supply circuit: Terminal, 1 cable 10...120 mm² tab outer diameter Ø: 25 mm, hardwired, without Gu wire terminal. power supply circuit: contact End, the cable 2 tab 10 ... 50 mm² outer diameter Ø: 25 mm, hardwired, without Gu wire terminal. | |
Tightening torque | Power circuit: 12 Nm power circuit: 12 Nm control circuit: 1.2 Nm (No 2 cross screw) control circuit: 1.2 Nm (Ø 6 flat ports) | |
height | 158 mm | |
width | 120 mm | |
depth | 136 mm | |
Control loop characteristics | AC 50/60 Hz | |
Rated impulse withstand voltage [Uimp] | 8 kV (according to IEC 60947) | |
protection cap | no | |
(~50Hz pull-in) power consumption (VA) | 280...350 VA on...20°C 60 Hz 280...350 VA on...20°C 50 Hz | |
product weight | 2.5 kg | |
Contactor compatibility features | M2 | |
model | LC1D | |