AM1-80/4 
      AM1-80/4 modular power surge protector is designed according to IEC and GB standards, AM series low-voltage power distribution system surge protector has strong surge discharge capability, the maximum discharge current per bit is 80kA (8/20μs) , suitable for all levels of protection of low-voltage power distribution systems, according to different power distribution systems (TT/TN/IT) can choose a variety of combinations.
	- High energy surge protection
 	- Built-in instantaneous overcurrent disconnect device
 	- Remote signaling alarm interface
 	- Pluggable Replacement Modules
 	- Failure detection indication
 	- The maximum discharge current of a single module is 80kA (8/20μs)
 	- Standard Modular Installation
 	- Built-in thermal circuit breaker
 	- Response speed: 10-9 seconds
 	- Plug-in foolproof design
 
Product performance parameters: 
						| model | 			AM1-80/4 | 		
					| SPD port | 			one port | 		
					| SPD category | 			Pressure limiting type | 		
					| Power Systems | 			TT-TN-IT | 		
					| Rated voltage Un | 			220V | 		
					| Maximum continuous operating voltage Uc | 			385V | 		
					| Nominal discharge current In(8/20μs) | 			40kA | 		
					| Maximum discharge current Imax (8/20μs) | 			80kA | 		
					| Protection level Up (8/20μs) | 			<2.4kV | 		
					| It is recommended to connect an overcurrent protection device in series | 			63A/35kA | 		
					| Response time | 			≤25ns | 		
					| size | 			2mods,DIN43880 | 		
					| Failure indication | 			Green: Normal Red: Failed | 		
					| Installation lead cross-sectional area | 			16-35mm 2 | 		
					| Installation method | 			35mm standard rail (EN50022/DIN46277-3) | 		
					| Working temperature | 			-40/85℃ | 		
					| Shell material | 			Thermoplastic material according to UL94 V-0 | 		
					| Shell protection class | 			IP20 | 		
					| Certification | 			CE RoHS | 		
					| Remote signaling alarm | 			Normally open/normally closed contact terminal (optional) | 		
					| Cross-sectional area of remote signaling terminal | 			Up to 1.5mm 2 solid wire/cord | 		
	
*Product parameters are subject to the actual product manual.The scope of products: 	- AM1-80/4: Main distribution cabinet of buildings with buried input of power line shielding
 	- Distribution boxes in buildings with outdoor incoming and outgoing line inputs
 	- External distribution cabinet/distribution box
 	- AM1-80/4 40kA (In), 80kA (Imax) four-module AC power lightning arrester
	  AM1-80/4-S 40kA (In), 80kA (Imax) four-module AC power lightning protection device, with remote signal alarm terminal 
 