Công ty TNHH công nghệ số Tân Thành

Đồng hồ nguồn phát tín hiệu, Victory genuine VICTOR11+ process signal source tester

  • Đăng ngày 19-11-2019 01:11:02 PM - 671 Lượt xem
  • Mã sản phẩm: VICTOR11+
  • Đồng hồ nguồn phát tín hiệu, Victory genuine VICTOR11+ process signal source tester

    Tình trạng sản phẩm:


    The basic features of the VICTOR 11+ process calibrator : measurement and output accuracy of 0.02%, measurement display of 5 bits, output display of 6 bits

    VICTOR 11+ process calibrator measurement function: DC voltage, DC current, frequency, on-off measurement, pressure

    Basic features of the VICTOR 11+ process calibrator :

    output basic accuracy of 0.02%, output display is 6 bits

    output functions: DC voltage, DC current, ohms, analog transmitter, thermocouple, RTD, frequency, pulse, switching

    . 3 DC current output, may provide 25% and 100% of the stepping manual, automatic and automatic stepping ramp output

    thermocouple output, high precision automatic cold junction compensation, °C or °F temperature display

    can be equipped with high-precision temperature probe, accuracy: ± 0.2 ° C

    large-screen LCD multi-data display, can display simultaneously: DC current and % value, thermocouple, thermal resistance temperature value and its corresponding division value, etc.

    , excellent operating performance keyboard configuration, display the set value corresponding to a bit and down keys set the LCD output

    Panel calibration technology allows calibration without opening the case

    with white LED backlight, with automatic backlight off and automatic power off function, suitable for field use

    VICTOR 11+ process calibrator output basic technical indicators

    Applicable for one year after calibration, 23 °C ±5 °C , 35 to 70% RH , accuracy = ± (set value % + range ]

     

    Features

    Range

    Output setting range

    Resolution

    Accuracy

    Remarks

    DC voltage DCV

    100mV

    -10.000 to 110.000mV

    μV

    0.02+0.01

    Maximum output current 0.5mA

    1000mV

    -100.00 to 1100.00mV

    10 μV

    0.02+0.01

    Maximum output current 2mA

    10V

    -1.0000 11.0000V

    0.1mV

    0.02+0.01

    Maximum output current 5mA

    DC current DCmA

    20mA

    0.000 22.000mA

    μA

    0.02+0.02

    External power supply to 28V at 20 mA , maximum load 1KΩ resistor analog transmitter

    Ohm OHM

    400 Ω

    0.00 Ω to 400.00 Ω

    0.01 Ω

    0.02+0.02

    Current is ±0.5~3mA

    When the current is ±0.1~0.5mA , add 0.1Ω additional error

    Lead resistance is not included in the accuracy

    4K Ω

    0.0000K Ω~ 4.0000KΩ

    0.1 Ω

    0.05+0.025

    Current is ±0.05~0.3mA

    Lead resistance is not included in the accuracy

    40K Ω

    0.000K Ω to 40.000KΩ

    Ω

    0.1+0.1

    Current is ±0.01mA

    Lead resistance is not included in the accuracy

    Thermocouple TC

    R

    °C to 1767 °C

    °C

    to 100 °C : 1.5 °C

    100 to 1767 °C : 1.2 °C

    Adopt ITS-90 temperature scale

    Accuracy does not include cold junction compensation error

    S

    °C to 1767 °C

    to 100 °C : 1.5 °C

    100 to 1767 °C : 1.2 °C

    K

    -200.0 °C to 1372.0 °C

    0.1 °C

    -200.0 -100.0 °C : 0.6 °C

    -100.0 to 400.0 °C : 0.5 °C

    400.0 1200.0 °C : 0.7 °C

    1200.0 1372.0 °C : 0.9 °C

    E

    -200.0 °C 1000.0 °C

    -200.0 -100.0 °C : 0.6 °C

    -100.0 600.0 °C : 0.5 °C

    600.0 1000.0 °C : 0.4 °C

    J

    -200.0 °C 1200.0 °C

    -200.0 -100.0:0.6°C

    -100.0 to 800.0 °C : 0.5 °C

    800.0 1200.0 °C : 0.7 °C

    T

    -250.0 °C 400.0 °C

    -250.0 to 400.0 °C : 0.6 °C

    N

    -200.0 °C 1300.0 °C

    -200.0 -100.0 °C : 1.0 °C

    -100.0 to 900.0 °C : 0.7 °C

    900.0 1300.0 °C : 0.8 °C

    B

    600 °C 1820 °C

    °C

    600 800 °C : 1.5 °C

    800 to 1820 °C : 1.1 °C

    L

    -200.0 °C 900.0 °C

    0.1 °C

    -200.0 to 0.0 °C : 0.7 °C

    0.0 to 900.0 °C : 0.5 °C

    U

    -200.0 °C 600.0 °C

    0.1 °C

    -200.0 to 0.0 °C : 0.7 °C

    0.0 to 600.0 °C : 0.5 °C

    Thermal resistance RTD

    Pt100 385

    -200.0 °C 800.0 °C

    0.1 °C

    -200.0 to 0.0 °C : 0.3 °C

    0.0 to 400.0 °C  : 0.5 °C

    400.0 800.0 °C : 0.8 °C

    Adopt ITS-90 temperature scale

    Pt100 Cu50 Cu10 excitation current is: ±0.5~3mA

    The excitation current is:

    0.5 °C additional error when ±0.1~0.5mA

     

    Pt200 Pt500 Pt1000 excitation current is ±0.05~0.3mA

    Lead resistance is not included in the accuracy

    Pt200 385

    -200.0 °C 630.0 °C

    -200.0 100.0 °C : 0.8 °C

    100.0 300.0 °C : 0.9 °C

    300.0 to 630.0 °C : 1.0 °C

    Pt500 385

    -200.0 °C 630.0 °C

    -200.0 100.0 °C : 0.4 °C

    100.0 to 300.0 °C : 0.5 °C

    300.0 to 630.0 °C : 0.7 °C

    Pt1000 385

    -200.0 °C 630.0 °C

    -200.0 to 100.0 °C : 0.2 °C

    100.0 to 300.0 °C : 0.5 °C

    300.0 to 630.0 °C : 0.7 °C

    Cu10

    -100.0 °C 260.0 °C

    1.8 °C

    Cu50

    -50.0 °C 150.0 °C

    0.6 °C

    Frequency FREQ

    100Hz

    1.00Hz~110.00Hz

    0.01Hz

    ±2 words

    to 11 Vp-p square wave level accuracy

    ±5% reading +0.5V

    50% duty cycle

    Load >100KΩ

    1KHz

    0.100KHz~1.100KHz

    1Hz

    10KHz

    1.0KHz~11.0KHz

    0.1KHz

    100KHz

    10KHz~110KHz

    2KHz

    ±5 words

    Pulse PULSE

    100Hz

    to 100000cycles

    1cyc

    ±2 words

    to 11 Vp-p square wave

    Level accuracy: ±5% reading +0.5V

    50% duty cycle load >100KΩ

    1KHz

    10KHz

    Switch SWITCH

    100Hz

    1.00Hz 110.00Hz

    0.01Hz

    ±2 words

    FET switch

    Maximum switching current voltage current: +28 V / 50mA

    1KHz

    0.100KH 1.100KHz

    1Hz

    10KHz

    1.0KHz 11.0KHz

    0.1KHz

    100KHz

    10KHz 110KHz

    2KHz

    ±5 words

    Other features of the VICTOR 11+ Process Calibrator :

    1. Internal temperature compensation sensor RJC, temperature range 0~50°C, compensation error £ ±0 . 5°C,

    , temperature probe accuracy: ± 0.2 ° C, probe temperature range: -20 ~ 100 ° C

    , the maximum voltage is applied between the output terminals and the ground: 30Vp-p

    , the maximum output current: about 25mA

    General characteristics of the VICTOR 11+ process calibrator :

    working temperature and humidity

    to 50 ° C, ≤ 80% RH without condensation

    40 to 50 ° C, ≤ 70% RH

    storage temperature and humidity: -25 ~ 60 ° C, ≤ 90% RH without condensation

    3  display and backlight

    Segment LCD dual display

    White LED backlight

    4  power supply

    *4 x 1.5V AAA alkaline battery powered

    *CA charger can charge Ni-Hi battery (optional)

    Automatic shutdown operation: can set the automatic shutdown time 0~60 minutes

    size and weight: 205 × 95 × 42 (mm), about 500g

    6  accessories: test pen, fuse

    VICTOR 11+ Process Calibrator

         

     



    TÂN THÀNH CAM KẾT

    • Sản phẩm, hàng hóa chính hãng.
    • Giá cả cạnh tranh.
    • Dịch vụ chăm sóc khách hàng tận tâm.

    Thông Tin Công Ty

    Đã thông báo

     


    THÔNG TIN LIÊN HỆ:
    -------------------------------
    CÔNG TY TNHH THIẾT BỊ CÔNG NGHIỆP TTH
    Trụ sở: số 124 ngõ 79 Yên Hoà-Cầu giấy-HN
    Kinh doanh 1 : 0816.861.515
    Kinh doanh 2 : 0836.861.515
    Email: tthkinhdoanh@gmail.com
    Email: tthkinhdoanh01@gmail.com

  • Kết nối với chúng tôi