Features |
AC current (through the jaw) |
Resolution | 0.01/0.1 A |
Precision | 2.0% ±5 digits (45-65 Hz) |
2.5% ±5 digits (65-400 Hz) |
Range | 60.00/600.0 A |
Crest factor (50Hz or 60Hz) | 2.5 MIN@220 A 3.0 MIN@180 A > 1.4 MIN@600 A CF>400 A increases by 2% |
AC voltage |
Resolution | 0.1 V |
Precision | 1.5% ± 5 digits |
Range | 600.0 V |
V dc |
Resolution | 0.1 V |
Precision | 1.5% ± 5 digits |
Range | 600.0 V |
ohm |
Resolution | 0.1/1/10 |
Precision | 1% ± 5 digits |
Range | 600/6000/60.00 kΩ |
capacitance |
Resolution | 0.1/1 μF |
Precision | 1% ± 4 digits |
Range | 100.0/1000 μF |
μA |
Resolution | 0.1 μA |
Precision | 1% ± 5 digits |
Range | 200 μA |
Contact temperature |
Resolution | 0.1 C/F |
Precision | 1% ± 8 digits |
Range | -10 to 400 °C (14 °F to 752 °F) |
On-off test buzzer |
Buzzer volume | 75 dBA (nominal) 15 cm from the front of the cabinet. |
Threshold | <=30 Ω |
Mechanical and general specifications |
The highest voltage between any terminal and ground | 1000 V |
type of battery | 2 AA alkaline batteries, NEDA 15A, IEC LR6 |
temperature | Operating temperature: -10 °C to +50 °C (14 °F to +122 °F) Storage temperature: -40 °C to +60 °C (-40 °F to +140 °F) |
Working humidity | Non-condensing (< 10 °C [50 °F]), relative humidity ≤90% (10 °C to 30 °C [50 °F to 86 °F]), relative humidity ≤75 % (30 °C to 40 °) C (86 °F to 104 °F)), relative humidity ≤ 45 % (40 °C to 50 °C (104 °F to 122 °F)) |
altitude | Working elevation: 3,000 m (9,842 ft) Storage elevation: 12,000 m (39,370 ft) |
size | 230 x 83.7 x 45.4mm (9.06 x 3.30 x 1.39 in) |
Weight (instrument only) | 419 g (15 oz) |
safety | IEC 61010-1, pollution degree 2 IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V IEC 61010-2-033: CAT III 1000 V / CAT IV 600 V |
Protection level | IEC 60529: IP30, when not in operation |
Radio frequency certification | FCC ID: T68-FBLE IC: 6627A-FBLE |
Electromagnetic compatibility (EMC) | International Standard: IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2 CISPR 11:1 Group, Class A, Korea (KCC): Class A Equipment (Industrial Broadcasting and Communication Equipment) USA (FCC): 47 CFR 15 B subsection. This product is considered to be exempt from inspection in accordance with Section 15.103. |
Temperature Coefficient | Above 28°C or below 18°C, an increase of 0.1 × per degree Celsius |